Operating Environment

For designed performance and safety of the HG1F, do not install the HG1F in the following environments:

• Where dust, briny air, or iron particles exist.

• Where oil or chemical splashes for a long time.

• Where oil mist is filled.

• Where direct sunlight falls on the HG1F.

• Where strong ultraviolet rays fall on the HG1F.

• Where corrosive or combustible gasses exist.

• Where the HG1F is subjected to shocks or vibrations.

• Where condensation occurs due to rapid temperature change.

• Where high-voltage or arc-generating equipment (electromagnetic contactors or circuit protectors) exists in the

vicinity.

Ambient Temperature

• Allow sufficient space for ventilation, and install the equipment away from heat sources.

• Allow at least 100mm between the HG1F and walls or other equipment.

• Do not install the HG1F where the ambient temperature exceeds the rated operating ambient temperature range.

When mounting the HG1F in such locations, provide a forced air-cooling fan or air-conditioner to keep the ambient

temperature within the rated temperature range.

• The HG1F is designed to install on a vertical plane so that natural air-cooling is provided. If you install it using any

other orientation, use forced-air cooling, or lower the ambient operating temperature.

HG1F Installation

• Make a panel cut-out on the panel with the dimensions shown below.

• Place the HG1F in a panel cut-out and fasten with the attached mounting clips at four places to a torque of 0.12 to

0.15 N•m uniformly.

• When installing the HG1F vertically, make sure that the power input terminal is on the upper side.

CAUTION

• Do not tighten excessively, otherwise the HG1F may warp and cause wrinkle on the display, or

impair the waterproof characteristics.

• If the mounting clips are tightened obliquely to the panel, the HG1F may fall off the panel.
• When installing the HG1F into a panel cut-out, make sure that the gasket is not twisted. Especially

when re-installing, take special care because any twists in the gasket will impair the waterproof
characteristics.

A

B

Unit: mm

A

B

Panel Cut-out

66.0

+1.0

0

137.0

+1.5

0

1.6 to 5.0

Panel

Mounting

Clip

HG1F

Make sure that the

power terminal is on the
upper side.