3 data configuration, Data configuration -5, Data log function – IDEC High Performance Series User Manual

Page 843

Advertising
background image

WindO/I-NV2 User’s Manual

14-5

1 Overview

14

Data Log Function

1.3 Data Configuration

The sampled data is composed of the sampling time, values of devices, and labels.
The relationship between the Data Log function settings and the sampled data is as follows.

1. Channel

The sampled data is in channel units. A maximum of 20 channels can be configured.

2. Data storage amount:

The amount of sampled data to save. The maximum amount that can be configured per
device differs according to the model. For details, refer to “Data Storage Amount” on
page 14-6.

3. Amount of data:

The amount of data configured for one channel. The maximum amount of data that can
be configured is 128. The maximum number of devices that can be configured to
sample values is 128 total for all channels.
For example, when the amount of data for channel 1 is set to 128, this is the maximum
amount total for all channels, so channel 2 through 20 cannot be configured.

4. Sampling time label:

When the sampled data is output as a CSV file, this label is displayed in the label row
for the sampling time column.

5. Data label:

When the sampled data is output as a CSV file, this label is displayed in the label row
for the data number columns.

Sampling

Time

Data001 Data002 Data003

01/01/2011

12:00:00

20

120

201

01/01/2011

12:10:00

21

121

204

01/01/2011

12:20:00

22

122

206

01/01/2011

12:30:00

23

123

206

01/01/2011

12:40:00

24

124

210

Data No. 1 seƫngs

Data No. 2 seƫngs

Data No. 3 seƫngs

Data No. 3 Value of Device

3. Amount of data

5. Data label

1. Channel 1 to 20

2. Data storage amount

Data No. 2 Value of Device

Data No. 1 Value of Device

Time the value of device was sampled

4. Sampling Ɵme label

Data log settings

Sampled data

Advertising