Liebert iCOM Microprocessor TM-10098 User Manual

Page 107

Advertising
background image

iCOM

Controls Training and Service Manual

Small Display Jumper Settings

Jumper

Type

Setting

P4

Manual Contrast

(Rev. 2 only)

* Shunt on Pins 2 & 3

P78

CAN Termination

* Shunt on Pins 2 & 3

P80

BDM Header

* open

P82

Watchdog

(Rev. 2 Only)

* Shunt on Pins 1 & 2


* Default Setting

Temperature/ Humidity Board DIP Switch #1 Settings

Position

Type

Setting

Notes

1

CAN Address

Off

On (if Sensor A)

2

CAN Address

Off

On (if Sensor B)

3

CAN Address

Off

On (if Sensor C)

4

CAN Address

Off

open

5 CAN

Address

On (Normal &

Constant Operation)

Off (Analog Mode)

6

CAN Address

Off (Normal Operation)

On (Analog Mode &

Constant Operation)

7 CAN

Baud

Off

open

8

CAN Baud

Off

open


Temperature/ Humidity Board Jumper Settings

Jumper

Type

Setting

P2

BDM Header

* open

P3

CAN Termination

* Shunt on Pins 2 & 3

P4 Programming

*

open


* Default Setting