Liebert iCOM Microprocessor TM-10098 User Manual

Page 24

Advertising
background image

iCOM

Control Training and Service Manual

3 Stage Electric Reheat – With Dead Band

Temp Set Point: 70

°F

Proportional Band: 8

°F

Dead Band: 2

°F

65 66 67 68 69 70

Decreasing Temperature

Temp Set Point - (1/2 Dead Band + 1/2 Proportional Band)

DB

Reheat 1 On

Reheat 3 On

Reheat 2 On

Reheat
3 Off

Reheat
2 Off

Reheat
1 Off




















Note: in the above example that the control band begins at the 70

°F temperature

set point and has a length of 5

°F, which is ½ of the programmed temperature dead

band value plus ½ of the programmed temperature proportional band value.

As the return air temperature decreases Reheat 1 is activated at 67.7

°F or ½ of

the dead band value plus 33% of the heating control band. If the return air
temperature continues to decrease Reheat 2 will activate at 66.4

°F or ½ of the

dead band value plus 66% of the heating control band. If the return air
temperature continues to decrease Reheat 3 will activate at 65

°F or ½ of the dead

band value plus 100% of the heating control band.

When the return air temperature starts to increase, Reheat 3 is deactivated at
66.4

°F or ½ of the dead band value plus 66% of the heating control band. Reheat

2 is deactivated at 67.7

°F or ½ of the dead band value plus 33% of the heating

control band. Reheat 1 is deactivated at 69

°F or ½ of the dead band value plus

0% of the heating control band.

Remember the temperature dead band value is used by the control to shift the
cooling on/ off operations away from the temperature set point.

23