Service menu: unit diary log – Liebert iCOM Microprocessor TM-10098 User Manual

Page 69

Advertising
background image

iCOM

Controls Training and Service Manual

Service Menu: Set Point Parameters S100 series: Page 2 of 2

Menu Line

Parameter

Default

Range

S112 Password

-

-

S113

Humidity Proportional Band

10%

1 – 20%

S114

Humidity Integration Time

0

0 – 5 minutes

S115

Humidity Deadband

0

0 – 50%

S116

DT Between Room / FC Type

Disable

Disable, Contact,

Value

S117

DT Between Room Air / FC Fluid

8ºF

0 - 36ºF

S118

Minimum CW Temp

Disable

Enable / Disable

S119

Minimum CW Temp Value

45ºF

32 - 68ºF

S120

S121

S122

Service Menu: Unit Diary Log

Parameter

Displays changes to the unit as performed and entered by

the service person or customer