iCOM

Controls Training and Service Manual

Service Menu: Set Alarm Parameters: Page 5 of 6

Menu Line

Parameter

S249

Password

S250

DELAY

EN-DIS

TYPE

S251

Working Hours Exceeded

-

En

Warning

S252

Smoke Detected

5 Sec

En

Alarm

S253

Water Under Floor

5 Sec

En

Alarm

S254

Cond Pump-High Water

5 Sec

En

Alarm

S255

Loss of Flow

5 Sec

En

Alarm

S256

Standby Glycol Pump On

5 Sec

En

Alarm

S257

Standby Unit On

5 Sec

En

Alarm

S258

Humidifier Problem

5 Sec

En

Alarm

S259

No Connection w/ Unit 1

-

En

Alarm

S260

Unit X Disconnected

-

En

Alarm


Service Menu: Set Alarm Parameters: Page 6 of 6

Menu Line

Parameter

S262

Password

S263

DELAY

EN-DIS

TYPE

S264

Customer Input 1

5 Sec

En

Alarm

S265

Customer Input 2

5 Sec

En

Alarm

S266

Customer Input 3

5 Sec

En

Alarm

S267

Customer Input 4

5 Sec

En

Alarm

S268

Call Service

5 Sec

En

Message

S269

High Temperature

5 Sec

En

Message

S270

Loss of Air Blower 1

5 Sec

En

Alarm

S271

Reheat Lockout

5 Sec

En

Message

S272

Humidifier Lockout

5 Sec

En

Message

S273

Humid + Reheat Lockout

5 Sec

En

Message

S274

Compressor(s) Lockout

5 Sec

En

Message