Liebert iCOM Microprocessor TM-10098 User Manual

Page 11

Advertising
background image

iCOM

Controls Training and Service Manual

A suggested tuning procedure is as follows:

1. Initially adjust the integral and derivative settings to 0% / degree-min

and 0% / degree / min..

2. Starting with 20% / degree, adjust the proportional setting in small

increments (10% steps) until the control sustains a constant hunting
action (the temperature swings are approximately the same amplitude
from one peak to the next).

3. Note the time in minutes between peaks of adjacent temperature

swings and the amplitude of the temperature swing (degrees above the
set point).

4. Adjust

the

proportional

control setting to about l/2 the value obtained in

Step 2.

5. Adjust the integral setting to a value calculated by the following

equation: approximate room load (in % full load) time between
peaks x peak amplitude x 4.

Note: If calculation results in a value of less than 1%, then set the
integral to 1%.

6. Adjust the derivative to a value calculated by the following equation:

time between peaks x 5%.


The above tuning procedure is only an approximation for an initial set of
adjustments and are based on the "average" room characteristics. Your particular
settings may need to be further adjusted for optimum PID control performance.

Some suggestions for additional tuning are as follows:

• If cooling output overshoot is occurring on load changes, decrease

the proportional setting or the derivative setting.

• If system hunting occurs with constant room load, decrease the

integral setting.

• If the control responds too slowly, resulting in large temperature

excursions on a load change, increase the proportional setting or
the derivative setting.

• If a constant temperature deviation exists between the

temperature and set point, increase the integral setting.

10

Advertising