Liebert iCOM Microprocessor TM-10098 User Manual

Page 80

Advertising
background image

iCOM

Control Training and Service Manual

Service Menu: Sensor Calibration/ Setup Parameters S600 series:
Page 1 of 3

Menu Line

Parameter

Range

S601 Password

-

S602

Return temperature

±17ºF

S603

Calibrated return temperature

32 - 122ºF

S604

Return humidity

±9.9%

S605

Calibrated return humidity

20 – 80%

S606

Digital Scroll 1 NTC

±17ºF

S607

Calibrated digital scroll 1 NTC

84 – 313ºF

S608

Digital Scroll 2 NTC

±17ºF

S609

Calibrated digital scroll 2 NTC

84 - 313ºF


Service Menu: Sensor Calibration/ Setup Parameters: Page 2 of 3

Menu Line

Parameter

Range

S612 Password

-

S613

Temperature sensor A

±17ºF

S614

Calibrated temperature sensor A

32 - 122ºF

S615

Humidity sensor A

±9.9%

S616

Calibrated humidity sensor A

20 – 80%

S617

Temperature sensor B

±17ºF

S618

Calibrated temperature sensor B

32 - 122ºF

S619

Humidity sensor B

±9.9%

S620

Calibrated humidity sensor B

20 – 80%

79