Control Training and Service Manual

Service Menu: Compressor 2 Settings Maintenance / Wellness Parameters:
Page 4 of 8

Menu Line

Parameter

Default

Range

S034 Password

-

-

S035

Number of Starts

-

0 – 32000

S036

Run Hours

-

0 – 32000

S037

Average Working Time

-

0 – 999 minutes

S038

Starts per Day Optimum

12

1 – 240

S039

Starts per Day Worst

240

1 – 240

S040

Number of HP Alarms

-

0 – 32000

S041

Number of LP Alarms

-

0 – 32000

S042

Number of OL Alarms

-

0 – 32000

S043

Number of DS HT Alarms

-

0 - 32000

S044

Actual Bonus

-

0 - 12


Service Menu: Electric Heater 1 Settings Maintenance / Wellness
Parameters: Page 5 of 8

Menu Line

Parameter

Default

Range

S045 Password

-

-

S046

Number of Starts

-

0 – 32000

S047

Run Hours

-

0 – 32000

S048

Average Run Time

-

0 – 999 minutes

S049

Starts per Day Optimum

24

1 – 240

S050

Starts per Day Worst

240

1 – 240

S051

Number of Alarms

-

0 – 32000

S052

Actual Bonus

-

0 - 12