Liebert iCOM Microprocessor TM-10098 User Manual

Page 88

Advertising
background image

iCOM

Control Training and Service Manual

Advanced Menu: Factory Settings Parameters: Page 6 of 6

Menu Code

Parameter

Default

Range

A145

Password

-

-

A146

Humidifier Model

No

No, external, IFS, IFL

A147

Humidity in Last
xx Hours

15hr

1 - 120 hours

A148

Prefill Time

IFS 30

IFL 60

1 - 120 seconds

A149

Fill Time

IFS 30

IFL 50

1 - 120 seconds

A150

Humidifier On
Time

IFS 8

IFL 10

1 - 60 minutes

A151

Dehum with
Compressor

2

1, 2, both

A152

Analog Output 1

Not used

* See note 3

A153

Analog Output 2

Not used

*See note 3

A154

Analog Output 3

Not used

* See note 3

A155

Analog Output 4

Not used

* See note 3


Note 1: LP threshold Phase 1 (A117):

If condenser ctrl (A132) = fan speed then setting is 50 psiA ; otherwise 75 psiA.

If the condenser control setting changes, the setting for A117 will be updated
automatically. If any of the sources (Refrigerant, Freecooling, Hotwater) changes,
the setting for A118 will be updated automatically.

Note 2: LP threshold Phase 1 (A118):

R22 (A102) + NO FC (A137) + NO Hotwater (S408) = 63 psiA

R22 (A102) + YES FC (A137) + NO Hotwater (S408) = 68 psiA

R22 (A102) + NO FC (A137) + YES Hotwater (S408) = 75 psiA

R22 (A102) + YES FC (A137) + YES Hotwater (S408) = 75 psiA

R407c (A102) + NO FC (A137) + NO Hotwater (S408) = 70 psiA

R407c (A102) + YES FC (A137) + NO Hotwater (S408) = 75 psiA

R407c (A102) + NO FC (A137) + YES Hotwater (S408) = 83 psiA

R407c (A102) + YES FC (A137) + YES Hotwater (S408) = 83 psiA


Note 3: The following components may be controlled with the Analog Outputs and
labeled as: Hot Water Reheat, 3P Valve, Fan Speed, Cooling, Cooling 1, Cooling
2, Heating and Not Used.

87