Liebert iCOM Microprocessor TM-10098 User Manual

Page 86

Advertising
background image

iCOM

Control Training and Service Manual

Advanced Menu: Factory Settings Parameters A100 series: Page 2 of 6



Advanced Menu: Factory Settings Parameters A100 series: Page 3 of 6

Menu Code

Function

Default

Range

A101

Password

-

-

A102

Refrigerant Type

R22

R22, R407C

A103

Main Fan Overload

Shut down

Shut down, Disable

A104

Loss of Airflow

Shut down

Shut down, Disable

A105

Number of Compressors

2

0, 1, 2

A106

Compressor Delay Time

0

0 - 120 Sec

A107

Compressor Minimum
On Time

3 Min

0 - 5 Min

A108

Compressor Minimum
Off Time

3 Min

0 - 5 Min

A109

Pump Down

Yes

No, Yes

A110

Capacity Control Type

Unloader

No, Unloader, HGBP,

Digital, Digital + TH

Menu Code

Parameter

Default

Range

A112

Password

-

-

A113

Digi Scroll Cycle

15

No, 10 - 30 Sec

A114

High Temperature Digi
Scroll

268°F

33 - 392°F

A115

Digi Scroll Switchback

250°F

33 - 392°F

A116

Low Pressure Device
Type

Analog Analog,

Switch

A117

Low Pressure Threshold
Phase 1

* See Note 1

0.0 - 145 psiA

A118

Low Pressure Threshold
Phase 2

* See Note 2

0.0 - 145 psiA



85