Liebert iCOM Microprocessor TM-10098 User Manual

Page 20

Advertising
background image

iCOM

Control Training and Service Manual

temperature is at least 8

°F below the return air temperature, or 3°F lower than the

return air temperature for two consecutive hours.

When the microprocessor decides that the return glycol fluid temperature is cold
enough the first cooling band is the modulating valve control method, and the
second band, added to the first band, is for the compressors as in the normal
2-Stage or 4-Stage control method. If the chilled glycol fluid temperature is not
cold enough the valve control band is replaced by the compressor band. If the
chilled glycol cooling capacity is reduced by a rise in the glycol fluid temperature,
the control band shrinks proportionally. This allows the compressor band to move
down as well. The following shows the Glycool operation at 100% capacity and
the Glycool at 50% capacity.

Glycool at 100% Capacity – No Dead Band






















Temp Set Point: 70

°

Proportional Band: 8

°

70 71 72 73 74 75 76 77 78 79

Increasing Temperature

Band 1 Glycool Valve

Band 2 Compressors

Valve
Closed

100%
Open

Cool 1 On

Cool 2 On

Temp Set Point + (1/2 Proportional Band + 1/2 Proportional Band)


19