Liebert iCOM Microprocessor TM-10098 User Manual

Page 81

Advertising
background image

iCOM

Controls Training and Service Manual

Service Menu: Sensor Calibration/ Setup Parameters: Page 3 of 3

Menu Line

Parameter

Default

Range

S623 Password

-

S624

Glycol sensor PTC or NTC

NTC

NTC or PTC

S625 Glycol

sensor

-

±17ºF

S626

Calibrated glycol sensor

-

4 – 113ºF

S627

Supply sensor PTC or NTC

NTC

NTC or PTC

S628

Supply sensor

-

±17ºF

S629

Calibrated supply sensor

-

32 - 122ºF

S630

Temperature sensor C

-

±17ºF

S631

Calibrated temperature sensor C

-

32 - 122ºF

S632

Humidity sensor C

-

±9.9%

S633

Calibrated humidity sensor C

-

20 – 80%



Service Menu: System / Network Setup Parameters Series S800:
Page 1 of 2, System View

Menu Line

Function

Default

Range

S801 Password

-

-

S802

Number of connected units

-

1 – 16

S803

Teamwork mode

No

No, 1, 2

S804

S805

U2U group

-

1 - 99

S806

S807

S808

S809

Configuration Safe Status

No

No, Save, Load

S810

Network Safe Status

-

No, Save, Load

S811 SW

version:

-