iCOM

Control Training and Service Manual

Service Menu: Set Alarm Parameters: Page 3 of 6

Menu Line

Parameter

S223

Password

S224

DELAY

EN-DIS

TYPE

S225

Main Fan Overload

10 Sec

En

Alarm

S226

Loss of Airflow

10 Sec

En

Alarm

S227

Clogged Filters

60 Sec

En

Warning

S228

High Room Temperature

10 Sec

En

Warning

S229

Low Room Temperature

10 Sec

En

Warning

S230

High Room Humidity

10 Sec

En

Warning

S231

Low Room Humidity

10 Sec

En

Warning

S232

High Temp Sensor A

10 Sec

En

Warning

S233

Low Temp Sensor A

10 Sec

En

Warning

S234

High Humid Sensor A

10 Sec

En

Warning

S235

Low Humid Sensor A

10 Sec

En

Warning

Service Menu: Set Alarm Parameters: Page 4 of 6

Menu Line

Parameter

S236

Password

S237

DELAY

EN-DIS

TYPE

S238

Comp 1 Overload

10 Sec

En

Alarm

S239

Comp 2 Overload

10 Sec

En

Alarm

S240

Comp 1 High Pressure

-

En

Alarm

S241

Comp 1 High Pressure

-

En

Alarm

S242

Comp 1 Low Pressure

-

En

Alarm

S243

Comp 2 Low Pressure

-

En

Alarm

S244

Comp 1 Pumpdown Fail

-

En

Alarm

S245

Comp 2 Pumpdown Fail

-

En

Alarm

S246

Dig Scroll1 High Temp

-

En

Alarm

S247

Dig Scroll2 High Temp

Alarm

77