User menu: set alarm parameters u200 series – Liebert iCOM Microprocessor TM-10098 User Manual

Page 64

Advertising
background image

iCOM

Control Training and Service Manual

User Menu: Set Alarm Parameters U200 series

Menu Line

Parameter

Default

Range

U201 Password

-

-

U202

Return Sensor Alarms

Enabled

Enabled or Disabled

U203

High Return Temperature

80ºF

33 - 210ºF

U204

Low Return Temperature

60ºF

33 - 210ºF

U205

High Return Humidity

60%

1 – 99%

U206

Low Return Humidity

40%

1 – 99%

U207

Sensor A Alarms

Disabled

Disabled or Enabled

U208

High Temperature Sensor A

90ºF

33 - 210ºF

U209

Low Temperature Sensor A

55ºF

33 - 210ºF

U210

High Humidity Sensor A

70%

1 - 99%

U211

Low Humidity Sensor A

30%

1 - 99%


User Menu: Sensor Data U300 series: Page 1 of 2

Menu Line

Parameter

Range

U301

Actual Temperature Setpoint

41 – 104ºF

U302

Actual Humidity Setpoint

20 – 80%

U303

Optional Sensor A Temperature

32 - 122ºF

U304

Optional Sensor A Humidity

20 – 80%

U305

Optional Sensor B Temperature

32 - 122ºF

U306

Optional Sensor B Humidity

20 – 80%

U307

Optional Sensor C Temperature

32 - 122ºF

U308

Optional Sensor C Humidity

20 – 80%

U309 Freecooling

Fluid

Temperature

4 - 113ºF

U310

DigiScroll 1 Temperature

84 - 313ºF

U311

DigiScroll 2 Temperature

84 - 313ºF

U312

Freecooling Status

Off, Start, On