Liebert iCOM Microprocessor TM-10098 User Manual

Page 18

Advertising
background image

iCOM

Control Training and Service Manual

As the return air temperature increases Cooling 1, lead compressor unloaded, is
activated at 72

°F or ½ of the dead band value plus 25% of the cooling control

band. If the return air temperature continues to increase Cooling 2, lag
compressor unloaded, will activate at 73

°F or ½ of the dead band value plus 50%

of the cooling control band. If the return air temperature continues to increase
Cooling 3, lead compressor unloaded, is activated at 74

°F or ½ of the dead band

value plus 75% of the cooling control band. If the return air temperature continues
to increase Cooling 4, lag compressor loaded, will activate at 75

°F or ½ of the

dead band value plus 100% of the cooling control band.

When the return air temperature starts to decrease, Cooling 4 is deactivated at
74

°F or ½ of the dead band value plus 75% of the cooling control band. If the

return air temperature continues to decrease Cooling 3 will be deactivate at 73

°F

or ½ of the dead band value plus 50% of the cooling control band. If the return air
temperature continues to decrease Cooling 2 will be deactivate at 72

°F or ½ of the

dead band value plus 25% of the cooling control band and Cooling 1 is
deactivated at 71

°F or 1/2 the dead band value plus 0% of the cooling control

band.

Remember the temperature dead band value is used by the control to shift the
cooling on/ off operations away from the temperature set point.