Liebert iCOM Microprocessor TM-10098 User Manual

Page 95

Advertising
background image

iCOM

Controls Training and Service Manual

028 HUM HRS

EXCEEDED

actual working hours of
the fan are higher than
the threshold set.

Warning

no

no

-

029 SUPPLY

SENSOR
FAILURE

sensor faulty or not
present, but needed from
control (supply limit
control enabled).

Warning

no no

-

031 ROOM

SENSOR
FAILURE

no valid data from the
std. sensor

Alarm

yes

yes

no

032 SENSOR A

FAILURE

no valid data from sensor
A

Warning

no no

-

034 NETWORK

FAILURE

the unit showing this
event has no connection
to the unit #1.

Warning

no

no

-

036 UNIT ON

fan motor in operation

Message

-

-

-

037 UNIT OFF

unit shut down

Message

-

-

-

038 SLEEP MODE unit is in sleep mode:

according to the settings
it is switched off or
working with a selectable
deadband.

Message

- -

-

039 STANDBY

MODE

unit is in standby (fan
off), waiting for a call to
start from the system (if
a unit fails or there is a
bus interruption).

Message

-

-

-

040 POWER ON

control is powered again
after a power off.

Message

- -

-

041 POWER OFF no power to the control:

this message will appear
at the next power on.

Message

-

-

-

042 Unit 1

disconnected

this event is created from
a coldfire display only:
the display doesn't find
unit #1

Warning

no no

-

043 Unit 2

disconnected

"

Warning

no

no

-

044 Unit 3

disconnected

" Warning

no

no

-

045 Unit 4

disconnected

"

Warning

no

no

-

046 Unit 5

disconnected

" Warning

no

no

-

047 Unit 6

disconnected

"

Warning

no

no

-

94