Temperature/ Humidity Board: All Units

This section deals with the single plug connection located on the system
temperature and humidity board. The temperature/ humidity board is supplied on
all systems with iCOM controls. The cable is plugged into Plug P67 on the unit
microprocessor board and transmits information using “CAN” – Controlled Area
Network communication. Troubleshooting is accomplished by observing an LED
located on the board. If the LED is glowing the board is good. The temperature
and humidity board is typically located in the unit return.

Humidity

Temperature

Sen

Sensor



Power

Supply





CAN Bus Connectors

Temperature/ Humidity Board


P67: Return Air Temperature/ Humidity Board

P67-1: CAN

communication

P67-6: CAN

communication


Temperature/ Humidity Assembly Housing