iCOM

Control Training and Service Manual

4 Stage Compressorized Cooling – No Dead Band

Temp Set Point: 70

°F

Proportional Band: 8

°F

70 71 72 73 74 75

Increasing Temperature

Cool 1 On

Cool 1 Off

Cool 4 On

Cool 3 Off

Temp Set Point + (1/2 Proportional Band)

Cool 2 On

Cool 3 On

Cool 4 Off

Cool 2 Off




















Note: in the above example that the control band begins at the 70

°F temperature

set point and has a length of 4

°F, which is ½ of the programmed temperature

proportional band value.

As the return air temperature increases Cooling 1, the lead compressor unloaded,
is activated at 71

°F or 25% of the cooling control band. If the return air

temperature continues to increase Cooling 2, the lag compressor unloaded is
activated at 72

°F or 50% of the cooling control band. If the return air temperature

continues to increase Cooling 3, the lead compressor is loaded at 73

°F or 75% of

the cooling control band. If the return air temperature continues to increase
Cooling 4, the lag compressor is loaded at 74

°F or 100% of the cooling control

band.

When the return air temperature starts to decrease, Cooling 4 is deactivated at
73

°F or 75% of the cooling control band. If the return air temperature continues to

decrease Cooling 3 is deactivate at 72

°F or 50% of the cooling control band. If the

return air temperature continues to decrease Cooling 2 is deactivate at 71

°F or

25% of the cooling control band and Cooling 1 is deactivated at the temperature
set point of 70

°F or 0% of the cooling control band.

15