Front and left side views of the triac, Schematic drawing for the triac – Liebert iCOM Microprocessor TM-10098 User Manual

Page 118

Advertising
background image

iCOM

Control Training and Service Manual

117

The triacs that Liebert uses are standard in the industry and are rated at a 2-amp
capacity. You can check these devices for proper operation while they are
connected in the circuit. If the load is removed from the device, you can get a
false reading from the meter. This is because the voltage potential is present and
is detected by the meter. When the load is applied to the device, the potential is
not detected by the meter. To test a triac for proper operation, energize the circuit
and connect the load.


Heat Si

B



Termina


Front

View

Left

Side

View

Front and Left Side Views of the Triac


As your view the triac from the front, the terminals are numbered as follows:

Terminal

nk

ody

ls

Connection

Left

#2 Connects to the Load

Middle

#1 Connects to the Transformer power

Right

G(ate) Connects to the Opto-Isolator


Below is a simple schematic drawing for the triac using Liebert symbols.









Schematic Drawing for the Triac

O

24 VAC
Transformer
Power

Load
Device

Opto

1

2

6

G

1

2

Triac

4