Humidity control program types, Humidity control – Liebert iCOM Microprocessor TM-10098 User Manual

Page 25

Advertising
background image

iCOM

Controls Training and Service Manual

Humidity Control


Humidification and/ or Dehumidification Required, in
Percent (%)

The humidity control programs for the

iCOM microprocessor is based on a

calculated percent (%RH) requirement for humidification and/ or dehumidification.
This percent (%RH) requirement is determined by the control type (algorithm)
selected by the user.

The two (2) user selectable humidity control programs are:

• Absolute Humidity, grains of moisture in the air
• Relative Humidity (%RH)


Humidity Control Program Types

Absolute (predictive) Humidity Control – Factory Default Setting

Absolute (predictive) humidity control is based on the moisture content in the
return air. The

iCOM microprocessor control automatically adjusts the humidity

control as the return air temperature deviates from the programmed temperature
set point. This calculation converts the return temperature and humidity values to
a moisture content value defined as either grains per cubic foot or grains per
pound. This recalculated content value is compared to the content control band
that is determined by the:

• Programmed temperature set point
• Programmed humidity set point in %RH
• Programmed

humidity

proportional band in %RH


This automatic adjustment results in a predictive humidity control response. With
absolute humidity control, the humidity control program is automatically adjusted
approximately 2% RH for each degree difference between the return air
temperature and the temperature set point. Note the following example:

24