iCOM

Control Training and Service Manual

2 Stage Compressorized Cooling – With Dead Band

Temp Set Point: 70

°F

Proportional Band: 8

°F

Dead Band: 2

°F

70 71 72 73 74 75

Increasing Temperature

Cool 1 On

Cool 1 Off

Cool 2 On

Cool 2 Off

Temp Set Point + (1/2 Dead Band + 1/2 Proportional Band)

DB




















Note: in the above example that the control band begins at the 70

°F temperature

set point and has a length of 5

°F, which is ½ of the programmed temperature dead

band value plus ½ of the programmed temperature proportional band value.

As the return air temperature increases Cooling 1 (lead compressor) is activated at
73

°F or ½ of the dead band value plus 50% of the cooling control band. If the

return air temperature continues to increase Cooling 2 (lag compressor) will
activate at 75

°F or ½ of the dead band value plus 100% of the cooling control

band.

When the return air temperature starts to decrease, Cooling 2 (lag compressor) is
deactivated at 73

°F or ½ of the dead band value plus 50% of the cooling control

band and Cooling 1 (lead compressor) is deactivated at 71

°F or ½ of the dead

band value plus 0% of the cooling control band.

Remember the temperature dead band value is used by the control to shift the
cooling on/ off operations away from the temperature set point.

Optional 4 - Stage Cooling, Two (2) Compressors with Unloaders

The basic temperature cooling control band is established at the temperature set
point with the length equal to ½ of the programmed temperature proportional band
divided by the number of cooling stages.

The Liebert DS units are supplied with two (2) compressors, each compressor is
rated at ½ of the unit capacity. Each compressor will be the semi-hermetic type