iCOM

Controls Training and Service Manual

of the heating proportional band. The third electric heating stage activates when
the return air temperature decreases to 100% of the heating proportional band.

The temperature controller deactivates the third heating stage when the return air
temperature increases to 66% of the heating proportional control band value. The
second heating is deactivated when the return air temperature increases to 33% of
the heating proportional control band value. The first heating stage is deactivated
when the return air temperature increases to the temperature set point value or
0% of the heating proportional control band value.

3 Stage Electric Reheat – No Dead Band

Temp Set Point: 70

°F

Proportional Band: 8

°F

65 66 67 68 69 70

Decreasing Temperature

Reheat 1 On

Temp Set Point - (1/2 Proportional Band)

Reheat 3 On

Reheat 2 On

Reheat
3 Off

Reheat
2 Off

Reheat
1 Off




















Note: in the above example that the control band begins at the 70

°F temperature

set point and has a length of 4

°F, which is ½ of the programmed temperature

proportional band value.

As the return air temperature decreases Reheat 1 is activated at 68.7

°F or 33% of

the heating control band. If the return air temperature continues to decrease
Reheat 2 will activate at 67.4

°F or 66% of the heating control band. If the return

air temperature continues to decrease Reheat 3 will activate at 66

°F or 100% of

the heating control band.

When the return air temperature starts to increase, Reheat 3 is deactivated at
67.4

°F or 66% of the heating control band, Reheat 2 is deactivated at 68.7°F or

33% of the heating control band and Reheat 1 is deactivated at the temperature
set point of 70

°F or 0% of the heating control band.