111

Fuse Board Layout: All Units

This section deals with the seven (7) plug connectors on the fuse board. The fuse
board is supplied on all systems with iCOM and is located in the low voltage
section of the unit. The tables in this section show all of the connections and
reference points for signal flow through these connectors.










Fuse Board


P4: 24 VAC Power

P4-1: Fuse 1

P4-3: Fuse 3

P4-2: Fuse 2

P4-4: Fuse 4


P24: T1 Transformer

P24-1: 24 VAC Gnd (T1)
P24-2: 24 VAC (T1)


P41: 24 VAC Power

P41-1:

24 VAC Gnd (T1)

P41-3:

24 VAC Gnd (not unit ground)

P41-2:

24 VAC (T1)

P41-4:

24 VAC


P42: Intelleslot

P42-1: 24 VAC Gnd (not unit ground)
P42-2: 24 VAC


P43: T6 Transformer

P43-1: 24 VAC Gnd (not unit ground)
P43-2: 24 VAC


P44: Jumper

E1: Transformer Secondary Ground (unit ground)