Control output triac legend, Control output opto-isolator legend – Liebert iCOM Microprocessor TM-10098 User Manual

Page 123

Advertising
background image

iCOM

Controls Training and Service Manual

Note: Use Pin 5 on the input opto-isolator with reference to the V- terminal
for voltage check. The voltage level is 5 VDC.

Control Output Opto-Isolator Legend:

Opto

Purpose

Opto

Purpose

U1

Reheat 1

U10

Compressor 2

U2

Reheat 2

U11

Econ-O-Cycle Relay (R5)

U3

Reheat 3

U12

Liquid Line Solenoid 1

U4

Humidifier

U13

Hot Gas Bypass 2

U5

Main Fan

U14

Compressor 1

U8

Liquid Line Solenoid 2

U17

CW Actuator

U9

Hot Gas Bypass 2

U18

CW Actuator Close


Note: Use Pin 4 on the output opto-isolator with reference to the correct
transformer neutral/ ground. The voltage level is 24 VAC.

Control Output Triac Legend:

Opto

Purpose

Opto

Purpose

Q1

Reheat 1

Q10

Compressor 2

Q2

Reheat 2

Q11

Econ-O-Cycle Relay (R5)

Q3

Reheat 3

Q12

Liquid Line Solenoid 1

Q4

Humidifier

Q13

Hot Gas Bypass 2

Q5

Main Fan

Q14

Compressor 1

Q8

Liquid Line Solenoid 2

Q17

CW Actuator

Q9

Hot Gas Bypass 2

Q18

CW Actuator Close