Liebert iCOM Microprocessor TM-10098 User Manual

Page 17

Advertising
background image

iCOM

Controls Training and Service Manual

The example below is based on a temperature set point of 70

°F with a control

band length of 4

°F, which is ½ of the programmed temperature proportional band

value.

STAGE

TEMPERATURE

Cool 1 ON

Set point plus 1

°F

Cool 2 ON

Set point plus 2

°F

Cool 3 ON

Set point plus 3

°F

Cool 4 ON

Set point plus 4

°F

Cool 4 OFF

Set point plus 3

°F

Cool 3 OFF

Set point plus 2

°F

Cool 2 OFF

Set point plus 1

°F

Cool 1 OFF

Set point



4 Stage Compressorized Cooling – With Dead Band

Temp Set Point: 70

°F

Proportional Band: 8

°F

Dead Band: 2

°F

70 71 72 73 74 75

Increasing Temperature

Cool 2 On

Cool 1 Off

Cool 4 On

Cool 3 Off

Temp Set Point + (1/2 Dead Band + 1/2 Proportional Band)

DB

Cool 1 On

Cool 3 On

Cool 4 Off

Cool 2 Off




















Note: in the above example that the control band begins at the 70

°F temperature

set point and has a length of 5

°F, which is ½ of the programmed temperature dead

band value plus ½ of the programmed temperature proportional band value.

16