iCOM

Controls Training and Service Manual

072 COMP 2

OVERLOAD

Compressor 2 stopped
because of overload

Alarm

no

yes

yes

(broken co
will remain

off)

079 UNIT

DISABLED

this message appears
after a critical alarm
(airflow, main fan
overload) and indicates
that the unit is operating
w/o humidifier or
electrical heaters.

Message

-

-

080 UNIT SHUT

DOWN

this message appears
after a critical alarm
(airflow, main fan
overload) and indicates
that the unit is shut down
due to the alarm.

Message

-

-

085 UNIT

SYNCHRONIS
ATION

a unit came back into the
network.

Message

- -

-

086 HUMIDIFIER

PROBLEM

humidifier
overtemperature or high
water level

Alarm

no

yes

088 DEHUM HRS

EXCEEDED

actual working hours of
dehumidification are
higher than the threshold
set.

Warning

no no

089 FC HRS

EXCEEDED

actual working hours of
freecooling are higher
than the threshold set.

Warning

no

no

-

091 COMP 1

PUMPDOWN
FAIL

Pump down of circuit 1
was not completed
(pressure value not
reached).

Alarm no yes yes

(broken co
will remain

off)

096 COMP 2

PUMPDOWN
FAIL

Pump down of circuit 2
was not completed
(pressure value not
reached).

Alarm

no

yes

yes

(broken co
will remain

off)

097 DIG SCROLL1

HIGH TEMP

Digital Scroll compressor
#1 shut off because of
high temperature (sensor
is inside the
compressor).

Alarm no yes yes

(broken co
will remain

off)