P34: reheat devices, P35: infrared humidifier devices – Liebert iCOM Microprocessor TM-10098 User Manual

Page 109

Advertising
background image

iCOM

Controls Training and Service Manual

P22: Glycool Valve (Std. Pressure Actuator)

P22-1:

24 VAC Out (Close Q18) P22-4:

DCV

Signal

P22-2: DCV

Signal

P22-5:

E2 (24 VAC Gnd)

P22-3:

24 VAC Out (Open Q17)

P22-6:

+5 VDC


P32: Compressor Devices

P32-1: 24 VAC Out (LLSV1)

P32-8:

24 VAC

P32-2: E1 (LLSV1)

P32-9:

24 VAC (HP1 Alarm)

P32-3: 24 VAC Out (LLSV2)

P32-10: 24 VAC Out (C1)

P32-4: 24 VAC Out (OL/ KL1/ HP1)

P32-11:

E1 (C1)

P32-5: 24 VAC Out (OL/ KL2/ HP2)

P32-12: 24 VAC Out (C2)

P32-6: 24 VAC (HP1)

P32-13: E2 (C2)

P32-7: 24 VAC (HP2)


P33: Compressor Devices

P33-1: 24 VAC Out (CUV1/ DSV1)

P33-7:

24 VAC (OL/ KL2 Alarm)

P33-2: E1 (CUV1/ DSV1)

P33-8:

24 VAC

P33-3: E2 (LLSV2)

P33-9:

24 VAC (HP2 Alarm)

P33-4: 24 VAC Out (CUV2/ DSV2)

P33-10:

P33-5: E2 (CUV2/ DSV2)

P33-11:

P33-6: 24 VAC (OL/ KL1 Alarm)

P33-12:


P34: Reheat Devices

P34-1: 24 VAC Out (RS1/ RS2/ RS3) P34-7:

no connection

P34-2: E3 (RS1/ RS2/ RS3)

P34-8:

24 VAC Out (RH3)

P34-3: E3 (GCD/ BR)

P34-9:

no connection

P34-4: 24 VAC Out (RH1/ HGRS)

P34-10: E3 (RH1/ HGRS/ RH2/ RH3)

P34-5: no connection

P34-11:

no connection

P34-6: 24 VAC Out (RH2)

P34-12: 24 VAC Out (GCD/ BR)


P35: Infrared Humidifier Devices

P35-1:

24 VAC Out (H)

P35-4:

E4 (HMV)

P35-2: E3

(H)

P35-5: E3

(HS3)

P35-3:

24 VAC Out (HMV)

P35-6:

24 VAC Out (HS3)


P36: Basic Unit Connections

P36-1: 24 VAC Out (Filter Clog)

P36-9:

no connection

P36-2: 24 VAC (Filter Clog Alarm)

P36-10: E2

P36-3: 24 VAC Out (MF)

P36-11: No connection

P36-4: 24 VAC Out (AS Switch)

P36-12: No connection

P36-5: 24 VAC (AS Alarm)

P36-13:

K3 (Common: TB75)

P36-6: 24 VAC (MF Ovld Alarm)

P36-14: K3 (N.O.: TB76/ R3)

P36-7:

24 VAC

P36-15:

K3 (N.C.)

P36-8: E4

(MF)

108