iCOM

Controls Training and Service Manual

The temperature controller deactivates the second stage of cooling (lag
compressor) when the return air temperature decreases to 50% of the cooling
proportional control band value. The first cooling stage (lead compressor) is
deactivated when the return air temperature decreases to the temperature set
point value or 0% of the cooling proportional control band value.

2 Stage Compressorized Cooling – No Dead Band

Temp Set Point: 70

°F

Proportional Band: 8

°F

70 71 72 73 74 75

Increasing Temperature

Cool 1 On

Cool 1 Off

Cool 2 On

Cool 2 Off

Temp Set Point + (1/2 Proportional Band)




















Note: in the above example that the control band begins at the 70

°F temperature

set point and has a length of 4

°F, which is ½ of the programmed temperature

proportional band value.

As the return air temperature increases Cooling 1 (lead compressor) is activated at
72

°F or 50% of the cooling control band. If the return air temperature continues to

increase Cooling 2 (lag compressor) will activate at 74

°F or 100% of the cooling

control band.

When the return air temperature starts to decrease, Cooling 2 (lag compressor) is
deactivated at 72

°F or 50% of the cooling control band and Cooling 1 (lead

compressor) is deactivated at the temperature set point of 70

°F or 0% of the

cooling control band.