Installation Instructions for Innotech Genesis Systems

Edition 011100

A-19

Figure A-18 shows the preferred connection point for the screen earth. Fitting it on the
screen terminal of one of a group of Digital Controllers gives optimum protection to the
greater number of Digital Controllers. The earthing point for the screen is at the first
Digital Controller in a group located together and supplied from one switchboard. This
preferred connection point does not remove the hazard that the screen voltage at point A
of Figure A-18 is not at earth voltage.

Figure A-18. Use of GENII Poly Switch Boards, Circuit 2

WARNING

ALTHOUGH AN IMPROVEMENT OVER PREVIOUS EARTH-
CONNECTION METHODS, THE CIRCUITS DESCRIBED IN
PARAGRAPH

A-4.2.10

STILL

DO

NOT

REMOVE

THE

ELECTRICAL

SHOCK

HAZARD

DESCRIBED

IN

THE

PREVIOUS PARAGRAPH.

Screen

1 2

Connect Screen

Screen

1 2

Connect Screen

Screen

1 2

Connect Screen

Poly-Switch

board only links

data. Screen

isolated.

Poly-Switch

board only links

data. Screen

isolated.

Only four outer

links fitted.

Screen is not

earthed.

Screen

1 2

Connect Screen

Switchboard or

Control Panel No. 2

Switchboard or

Control Panel No. 1

A

Poly-Switch

board only links

data. Screen

isolated.