Installation Instructions for Innotech Genesis Systems

Edition 011100

2-12

2-4.3.

ADDITIONAL INSTALLATION GUIDELINES.

For installation of the

Genesis II Digital Controller or GENII MPC system with REMs, observe the applicable
installation guidelines in Paragraph 2-3.2 and the following specific guidelines:

Although the Genesis II Digital Controller should be mounted in a location providing easy

access to operating controls and indicators, this requirement does not apply to the Genesis
I Digital Controller and GENII MPC which have no external controls or indicators.

Ensure the Digital Controller has been upgraded to Version 4.0 firmware to support the

REMs.

Install the GENII RMI on a DIN rail mounting adjacent to the Digital Controller or GENII

MPC. The cable between the RMI and the Digital Controller/MPC must not exceed 1
metre in length.

The Digital Controller/MPI can have only one GENII RMI connected to it.

Local Expansion Modules cannot be connected to a Digital Controller/MPC that has a

GENII RMI module connected to it.

REMs should be mounted in locations such that the cable run between the GENII RMI

and the REMs does not exceed 500 metres in length.

REM units should be mounted on DIN rails in cabinets approved for switchgear or

industrial control equipment.

Ensure that the types and quantities of REMs assigned to a controller are in accordance

with Paragraph 2-4.1.