Installation Instructions for Innotech Genesis Systems
Edition 011100
2-12
2-4.3.
ADDITIONAL INSTALLATION GUIDELINES.
For installation of the
Genesis II Digital Controller or GENII MPC system with REMs, observe the applicable
installation guidelines in Paragraph 2-3.2 and the following specific guidelines:
•
Although the Genesis II Digital Controller should be mounted in a location providing easy
access to operating controls and indicators, this requirement does not apply to the Genesis
I Digital Controller and GENII MPC which have no external controls or indicators.
•
Ensure the Digital Controller has been upgraded to Version 4.0 firmware to support the
REMs.
•
Install the GENII RMI on a DIN rail mounting adjacent to the Digital Controller or GENII
MPC. The cable between the RMI and the Digital Controller/MPC must not exceed 1
metre in length.
•
The Digital Controller/MPI can have only one GENII RMI connected to it.
•
Local Expansion Modules cannot be connected to a Digital Controller/MPC that has a
GENII RMI module connected to it.
•
REMs should be mounted in locations such that the cable run between the GENII RMI
and the REMs does not exceed 500 metres in length.
•
REM units should be mounted on DIN rails in cabinets approved for switchgear or
industrial control equipment.
•
Ensure that the types and quantities of REMs assigned to a controller are in accordance
with Paragraph 2-4.1.