Installation Instructions for Innotech Genesis Systems

Edition 011100

4-10

The output circuits are then checked for the opposite condition. For circuits using the NC
contacts, the wire going the C terminal is temporarily disconnected and the associated
device is checked to make sure it is de-energised. For circuits using the NO contacts, a
jumper wire is temporarily connected between the NO and C terminals; the associated
device is checked to make sure it is energised.

Figure 4-4. Checking Digital Output Wiring.

4

41 42 43 44 45 46 47

NO

NO

NO

C

C

NC

NC

V

AC

V

DC

0V

+

-

V

AC

V

DC

240V

+

-

L1

L1

L2

L2

GENESIS II

DIGITAL

CONTROLLER

TERMINALS

EXTERNAL

DEVICE

DIGITAL

OUTPUT

1

DIGITAL

OUTPUT

2

4

41 42 43 44 45 46 47

NO

NO

NO

C

C

NC

NC

V

AC

V

DC

240V

+

-

V

AC

V

DC

0V

+

-

L1

L1

L2

L2

JUMPER

WIRE

DISCONNECT

COMMON

WIRE