Installation Instructions for Innotech Genesis Systems

Edition 011100

A-4

A-4.1.2.

Linking Networks in Different Locations.

When linking networks in

different buildings, or when linking modules supplied from different switchboards, isolation
must be provided to eliminate earth loops. Use a GENII RPTR Repeater Module to isolate
the networks (Figure A-3). Note that the cable going to the more remote zone is always
connected to Port 2 of the Repeater Module.

Figure A-3. Linking Networks in Different Locations.

A-4.1.3.

Multi-Network Arrangement.

Figure A-4 shows a multi-network

arrangement consisting, effectively, of four separate networks. Each is wired in a bus
topology and each could be up to 1000 metres long. The networks are linked by the
electronics in the Repeater Modules. The GENII MPI Modem and Printer Interface does
not need to be an isolated version but it should be noted that the Comms cable connecting
Ports 2 of the Repeater Module will be earthed through the MPI via the PC and the printer.
The correct port of the Repeater Modules must be used to maintain the integrity of isolation
between sections.

Figure A-4. Multi-Network Arrangement.

Note: Maximum Cable Length = 1000 Metres

Zone A

Zone B

Repeater

See Note

See Note

1

2

Zone B

Zone A

Repeater

See Note

See Note

1

2

Note:

Maximum Cable

Length =

1000 Metres

Repeater

See Note

S

ee

No

te

See Note

Repeater

2
1

Repeater

See Note

2
1

2
1

MPI

PRINTER

MODEM

PC