Installation Instructions for Innotech Genesis Systems
Edition 011100
3-28
The group of five terminals at the lower left of the module serves two separate functions.
The two terminals on the left of the group (P+ and P-) provide a 12Vdc source for digital
input signals (Figure 3-16). The three terminals on the right side of the group are the
COMMS cable connections:
•
C+ = RS 485 (+) Signal
•
C- = RS 485 (-) Signal
•
SHLD = Comms cable shield
The MP REM accepts up to four isolated, switched-contact, digital inputs. Refer to Table
3-18 for DIGITAL INPUT signal terminal identification. The digital inputs can use the P+
and P- terminals as a 12Vdc signal-source or, alternatively, an external 24Vac source can be
used. Figure 3-16 shows how the digital inputs can be wired in either of the two
configurations.
Table 3-18. MP REM Digital Input Signal Connections.
SIGNAL
POSITIVE
TERMINAL
NEGATIVE
TERMINAL
Digital Input 1
DI#1+
DI#1-
Digital Input 2
DI#2+
DI#2-
Digital Input 3
DI#3+
DI#3-
Digital Input 4
DI#4+
DI#4-
Input from a single 10k
Ω
thermistor temperature sensor connects to the SENSOR
connection block at the lower right corner of the module. The two sensor leads connect to
Terminals TH1 and TH2. The thermistor cable screen connects to the SHLD terminal.