Innotech Genesis V4 System User Manual

Page 61

Advertising
background image

Installation Instructions for Innotech Genesis Systems

Edition 011100

4-6

Figure 4-2. Checking Digital Input Wiring.

NOTE

The following procedures assume the digital inputs are driven by
Normally Open contacts. For digital inputs driven by Normally
Closed contacts, the voltage indications should reverse.

a.

Ensure power to the Digital Controller is turned off.

b.

Set the digital voltmeter range to read at least 25 Volts.

c.

Connect the voltmeter to the first digital input channel (Terminals 3 and 4 for the
Genesis II Digital Controller). Observe polarity, ensuring the red (+) test lead is
connected to the positive terminal (3) and the black (-) test lead is connected to the
negative terminal (4).

10 11 12 13 14 15 16 17 18

3 4 5 6 7 8 9

AC

SOURCE

DC

SOURCE

JUMPER WIRE

V

AC

V

DC

24V

+

-

V

AC

V

DC

24V

+

-

CHECKING DC SOURCE

CHECKING AC SOURCE

DIGITAL CONTROLLER

1 2

Advertising