L = 240vac supply, N = neutral, Module viewed from the rear – Innotech Genesis V4 System User Manual
Page 53
Installation Instructions for Innotech Genesis Systems
Edition 011100
3-27
Figure 3-15. MP REM Multipoint Module.
POWER and DIGITAL OUTPUTS terminals are arranged across the top edge of the
module’s main circuit board. COMMS, DIGITAL INPUTS and SENSOR inputs are
arranged along the bottom edge of the board.
Power requirements are 240Vac,
±
10% at 50/60Hz. Power consumption is 7VA maximum.
The three terminals of the POWER connector block are
•
L = 240Vac Supply
•
N = Neutral
•
E = Earth
The DIGITAL OUPUTS (relay) terminals are listed in Table 3-17. Relay contacts are rated
at 2 Amperes.
Table 3-17. MP REM Output Relay Connections.
RELAY
COMMON
CONTACT
NOT
CONNECTED
NORMALLY
OPEN
Relay 1
DI1 C
DI1 I
DI1 O
Relay 2
DI2 C
DI2 I
DI2 O
Relay 3
DI3 C
DI3 I
DI3 O
Relay 4
DI4 C
DI4 I
DI4 O
Relay 5
DI5 C
DI5 I
DI5 O
SHLD
L
C
I
O
O
O
O
I
I
I
C
C
C
O
I
C
N
E
+DI#1-
+DI#2-
+DI#3-
+DI#4-
TH1 TH2 SHLD
COMMS
POWER
DIGITAL OUTPUTS
DI 1
DI 2
DI 3
DI 4
DI 5
DIGITAL INPUTS
SENSOR
P+
P-
C-
C+
MODULE VIEWED FROM THE REAR