Installation Instructions for Innotech Genesis Systems

Edition 011100

3-27

Figure 3-15. MP REM Multipoint Module.

POWER and DIGITAL OUTPUTS terminals are arranged across the top edge of the
module’s main circuit board. COMMS, DIGITAL INPUTS and SENSOR inputs are
arranged along the bottom edge of the board.

Power requirements are 240Vac,

±

10% at 50/60Hz. Power consumption is 7VA maximum.

The three terminals of the POWER connector block are

L = 240Vac Supply

N = Neutral

E = Earth

The DIGITAL OUPUTS (relay) terminals are listed in Table 3-17. Relay contacts are rated
at 2 Amperes.

Table 3-17. MP REM Output Relay Connections.

RELAY

COMMON

CONTACT

NOT

CONNECTED

NORMALLY

OPEN

Relay 1

DI1 C

DI1 I

DI1 O

Relay 2

DI2 C

DI2 I

DI2 O

Relay 3

DI3 C

DI3 I

DI3 O

Relay 4

DI4 C

DI4 I

DI4 O

Relay 5

DI5 C

DI5 I

DI5 O

SHLD

L

C

I

O

O

O

O

I

I

I

C

C

C

O

I

C

N

E

+DI#1-

+DI#2-

+DI#3-

+DI#4-

TH1 TH2 SHLD

COMMS

POWER

DIGITAL OUTPUTS

DI 1

DI 2

DI 3

DI 4

DI 5

DIGITAL INPUTS

SENSOR

P+

P-

C-

C+

MODULE VIEWED FROM THE REAR

Advertising