Innotech Genesis V4 System User Manual

Page 23

Advertising
background image

Installation Instructions for Innotech Genesis Systems

Edition 011100

2-9

Figure 2-9. DIN Rail Dimensions.

2-3.2.

INSTALLATION GUIDELINES.

To ensure continued reliable operation of

the Genesis II System, the following installation guidelines should be observed:

The Genesis II Digital Controller should be installed in a position that provides easy

access to the front panel and sufficient room for power, and input/output cabling. Also,
the Digital Controller should be mounted such that the controls are in easy reach of the
user.

Install LEMs as close as possible to the Digital Controller and side-by-side on the DIN

rail. Refer to Paragraph 2-3 and Figure 2-8.

Placement of the Genesis II Digital Controller should take into account the optimum

viewing angle of the Liquid Crystal Display (LCD), which is approximately 45

o

vertically

and 90

o

horizontally (see Figure 2-10).

Do not mount any unit of the system near high voltage, high current cables or sources of

strong radio frequency emissions such as transmitter antenna cables.

The ambient temperature of the Digital Controller and LEMs at the installation site should

not exceed the 0-40ºC temperature range. Ideally, the installation site should have a stable
ambient temperature close to 20

o

C.

Mount the units in an area with minimum vibration and minimum exposure to mechanical

damage.

Figure 2-10. Digital Controller Display, Viewing Angles.

ALL DIMENSIONS ARE IN MILLIMETRES

15

35

25

Mounting Slot

18 X 5.2

SIDE VIEW

TOP VIEW

90 DEGREES

45

DEGREES

Advertising