Innotech Genesis V4 System User Manual
Page 23
Installation Instructions for Innotech Genesis Systems
Edition 011100
2-9
Figure 2-9. DIN Rail Dimensions.
2-3.2.
INSTALLATION GUIDELINES.
To ensure continued reliable operation of
the Genesis II System, the following installation guidelines should be observed:
•
The Genesis II Digital Controller should be installed in a position that provides easy
access to the front panel and sufficient room for power, and input/output cabling. Also,
the Digital Controller should be mounted such that the controls are in easy reach of the
user.
•
Install LEMs as close as possible to the Digital Controller and side-by-side on the DIN
rail. Refer to Paragraph 2-3 and Figure 2-8.
•
Placement of the Genesis II Digital Controller should take into account the optimum
viewing angle of the Liquid Crystal Display (LCD), which is approximately 45
o
vertically
and 90
o
horizontally (see Figure 2-10).
•
Do not mount any unit of the system near high voltage, high current cables or sources of
strong radio frequency emissions such as transmitter antenna cables.
•
The ambient temperature of the Digital Controller and LEMs at the installation site should
not exceed the 0-40ºC temperature range. Ideally, the installation site should have a stable
ambient temperature close to 20
o
C.
•
Mount the units in an area with minimum vibration and minimum exposure to mechanical
damage.
Figure 2-10. Digital Controller Display, Viewing Angles.
ALL DIMENSIONS ARE IN MILLIMETRES
15
35
25
Mounting Slot
18 X 5.2
SIDE VIEW
TOP VIEW
90 DEGREES
45
DEGREES