A-4.2.12.

GENII MPI with Non-Isolated Comms.

When using a GENII MPI

Modem and Printer Interface which has standard RS485 ICs, the RS485 connection is not
isolated. Connecting a printer or a PC to the MPI will earth it. To prevent earth loops all
other devices on that section of Comms cable must isolate the screen from the electrical
earth.

Figure A-23 shows one local and three remote Genesis II non-isolated Digital Controllers,
all of which have only the four outer links fitted. In this situation it is better to fit GENII
485I Isolated RS485 Comms cards to the three remote Digital Controllers.

Figure A-23. Use of GENII MPI, Circuit 1.

Switchboard or

Control Panel No. 2

Screen

1 2

Connect Screen

Screen

1 2

Connect Screen

Switchboard or

Control Panel No. 1

Screen

1 2

Connect Screen

Only four outer

links fitted.

Screen is not

earthed.

Screen

1 2

Connect Screen

Only four outer

links fitted.

Screen is not

earthed.

Only four outer

links fitted.

Screen is not

earthed.

Only four outer

links fitted.

Screen is not

earthed.

Printer

Modem

MPI

Printer

PC

M

C