Installation Instructions for Innotech Genesis Systems

Edition 011100

A-22

A-4.2.11.

Genesis II Comms. Isolated by Repeater.

A GENII RPTR Repeater

Module provides electrical isolation for all data conductors and for the screen of the
Comms cable connected to Port 2 (Figure A-21). Therefore, Port 2 must be used to connect
the Comms cable going to the remote devices. The screen of the cable connected to Port 2
should be earthed at a device in Control Panel No. 2. Preferably, the earthing point should
be at the first device that the cable connects to in Control Panel No. 2.

If the screen is earthed by a local device, then the screen should not be connected to the
SHLD terminal of Port 1; this is to prevent an earth loop.

Figure A-21. Use of GENII RPTR Repeater Module, Circuit 1.

Switchboard or

Control Panel No. 2

Screen

1 2

Connect Screen

Screen

1 2

Connect Screen

Switchboard or

Control Panel No. 1

Screen

1 2

Connect Screen

Only four outer

links fitted.

Screen is not

earthed.

Only four outer

links fitted.

Screen is not

earthed.

Only four outer

links fitted.

Screen is not

earthed.

Screen

1 2

Connect Screen

Six outer links

fitted. Screen is

earthed via
Terminal 2.

E

art
h

2

1

Isolated

Not

Isolated

Repeater

Screen is NOT connected

on Port No. 1.