Innotech Genesis V4 System User Manual

Page 32

Advertising
background image

Installation Instructions for Innotech Genesis Systems

Edition 011100

3-6

Table 3-2. Genesis II Digital Controller Digital Inputs.

TERMINAL

SIGNAL

TERMINAL

SIGNAL

POSITIVE SIDE

NEGATIVE SIDE

3

DI1+

4

DI1

5

DI2+

6

DI2

7

DI3+

8

DI3

9

DI4+

10

DI4

11

DI5+

12

DI5

13

DI6+

14

DI6

15

DI7+

16

DI7

17

DI8+

18

DI8

3-3.1.3.

Digital Outputs.

Each of the Genesis II Digital Controller’s eight digital

output channels (Terminals 41–64) consists of a single-pole, double-throw (SPDT) relay.
Three terminals assigned to each channel represent the associated relay’s Normally Open
(NO), Common (C) and Normally Closed (NC) contacts.

Digital output relay contacts are rated at 240Vac, 2A. Good practice is to use pilot relays
for the actual switching functions, particularly when it applies to inductive loads such as
coils, solenoids and motors. This protects the relays of the digital output channel and has
the advantage of allowing the pilot relays to be installed adjacent to the controlling
switchgear.

Refer to Table 3-3 for digital output terminal number assignments.

Table 3-3. Genesis II Digital Controller Digital Outputs.

TERMINAL

SIGNAL

TERMINAL

SIGNAL

TERMINAL

SIGNAL

NORMALLY

OPEN (NO)

COMMON (C)

NORMALLY

CLOSED (NC)

41

DO1NO

42

DO1C

43

DO1NC

44

DO2NO

45

DO2C

46

DO2NC

47

DO3NO

48

DO3C

49

DO3NC

50

DO4NO

51

DO4C

52

DO4NC

53

DO5NO

54

DO5C

55

DO5NC

56

DO6NO

57

DO6C

58

DO6NC

59

DO7NO

60

DO7C

61

DO7NC

62

DO8NO

63

DO8C

64

DO8NC

Advertising