Installation Instructions for Innotech Genesis Systems

Edition 011100

A-27

Figure A-26. Voltage Check, GENII MPI with Isolated/Non-Isolated RS485.

Figure A-27. Voltage Check, GENII RPTR Repeater Module.

Measure all voltages to the metal shell of a DB connector on the MPI with the MPI

connected to a PC or Printer which is plugged into a standard power point (outlet).

MODEM

PC

PRINTER

V

AC

V

DC

3.5

MPI With Non-Isolated RS485

MODEM

PC

PRINTER

V

AC

V

DC

24V

MPI With Isolated RS485

Measure AC and DC
voltages: Should be
less than 3.5Vac and
between +10Vdc and
-5Vdc.

Measure AC and DC
voltages: Should be
less than 24Vac and
between +33Vdc and
-33Vdc.

Comms Cables for Port 2

V

AC

V

DC

24V

1

2

Isolated from

internal circuit

Connected to

internal circuit

EA
R

TH

L

N
E

Measurements Made

With Earth Wire

Connected

Comms Cables for Port 1

V

AC

V

DC

3.5V

1

2

Isolated from

internal circuit

Connected to

internal circuit

EA
R

TH

L

N
E

Measure AC and DC
voltages: Should be
less than 3.5Vac and
between +10Vdc and
-5Vdc.

Measure AC and DC
voltages: Should be
less than 24Vac and
between +33Vdc and
-33Vdc.