Installation Instructions for Innotech Genesis Systems
Edition 011100
3-17
CAUTION
LOOP POWERED 4-20MA INPUTS MUST NOT BE USED WITH
THE GEN II ANALOGUE INPUT MODULE.
3-4.1.2.
DIM Digital Input Modules.
Each DIM (Figure 3-8) provides an
expansion capability of four additional digital input channels. The DIM does not have
power terminals since operating power is supplied from the controller by way of the LEM
cable.
Figure 3-8. Digital Input Module.
Digital input terminals for the DIM are listed in Table 3-10. It should be noted that digital
input signals must have an amplitude of 24Vac/Vdc powered from an external source. If
the input signals are from a DC source, ensure the correct polarity of connections as listed
in Table 3-10. Avoid running the signal cable through ducts where adjacent cables may be
connected to digital or other switching devices.
Table 3-10. Digital Input Module Signal Connections.
TERMINAL
SIGNAL
TERMINAL
SIGNAL
ACTIVE
REFERENCE
A
DI1+
B
DI1
−
C
DI2+
D
DI2
−
E
DI3+
F
DI3
−
G
DI4+
H
DI4
−
GENESIS II
DIGITAL INPUT MODULE
LEM CABLE
CONNECTOR
DIGITAL INPUTS