4.2.4. ai rem analogue input module – Innotech Genesis V4 System User Manual

Page 48

Advertising
background image

Installation Instructions for Innotech Genesis Systems

Edition 011100

3-22

Figure 3-11. RMI Remote Module Interface.

3-4.2.4.

AI REM Analogue Input Module.

The AI REM (Figure 3-12) is

powered by 24Vac

±

10% at 4VA maximum. It provides for six analogue inputs from field

equipment. Each analogue input circuit has a socket for fitting an AISC, which defines the
input type and range selection. Installing the AISCs is part of the commissioning process

and is explained in Section 4.

Figure 3-12. AI REM Analogue Input Module.

The RS485 Comms connection block is in the upper right section of the module and the
End of Cable Jumper is next to it.

Analogue input terminals for the AI REM are listed in Table 3-12. Analogue input cables
should be run using twisted pair, shielded cable. The screens are to be connected to either
of the two terminals marked SCREEN.

GENESIS II
REMOTE MODULE INTERFACE

TX

RX

REM CABLE

CONNECTOR

RS485 COMMS

CONNECTIONS

END OF

CABLE

JUMPER

COMMS EARTH

CONNECTION

GENESIS
ANALOG INPUT
Remote Expansion Module

1 2 3

SCREEN

A BC D E F G H I J K L

SCREEN

A1

A2

A3

A4

A5

A6

+

+

+

+

+

+

_

_

_

_

_

_

RS485 COMMS

CONNECTIONS

END OF

CABLE

JUMPER

POWER

ANALOGUE INPUT

CONNECTIONS