Installation Instructions for Innotech Genesis Systems
Edition 011100
4-8
g.
Observe the voltmeter. It should indicate 0Vdc with the input switch closed.
h.
Release the manually-closed contacts. If a jumper wire was used in Step f., remove
the jumper wire.
i.
Repeat Steps d. through h. for the remaining digital input channels.
j.
Remove operating power from the REM.
k.
Reconnect the RS485 cable that was disconnected in Step a.
Figure 4-3. Checking Dry Contact Inputs.
V
AC
V
DC
0V
+
-
SWITCH CLOSED
V
AC
V
DC
5V
+
-
SWITCH OPEN
GENII DI REM
GENII DI REM