Innotech Genesis V4 System User Manual
Page 50
Installation Instructions for Innotech Genesis Systems
Edition 011100
3-24
Table 3-12. AI REM Analogue Input Signal Connections.
TERMINAL
SIGNAL
TERMINAL
SIGNAL
ACTIVE
REFERENCE
A
AI1+
B
AI1
−
C
AI2+
D
AI2
−
E
AI3+
F
AI3
−
G
AI4+
H
AI4
−
I
AI5+
J
AI5
−
K
AI6+
L
AI6
−
SCREEN
Common Screens
3-4.2.5.
AO REM Analogue Output Module.
The AO REM (Figure 3-13)
provides up to five analogue outputs. Analogue output terminals are located at the bottom
of the module; output signal connections are listed in Table 3-13. Analogue output cables
should be run using twisted pair shielded cable. The screens should be connected to the
signal’s negative output terminal (B, D, F, H or J) in each case.
Figure 3-13. AO REM Analogue Output Module.
Table 3-13. AO REM Analogue Output Signal Connections.
TERMINAL
SIGNAL
TERMINAL
SIGNAL
A
AO1+
B
AO1- & Screen
C
AO2+
D
AO2- & Screen
E
AO3+
F
AO3- & Screen
G
AO4+
H
AO4- & Screen
I
AO5+
J
AO5- & Screen
GENESIS
ANALOG OUTPUT
Remote Expansion Module
1 2 3
A B C D E F G H I J
RS485 COMMS
CONNECTIONS
END OF
CABLE
JUMPER
POWER
ANALOGUE
OUTPUT
CONNECTIONS