Lenze PC-based Automation Industrial PC User Manual

Page 121

Advertising
background image

2.5 EN - 01/2012

L

121

Industrial PC | Parameter setting & configuration

Visualisation with »VisiWinNET®«

Configuration of the OPC tunnel

Preparation

Read in the CF card of the visualisation IPC on your PC using a card reader

or

Establish an FTP connection between your PC and the visualisation IPC



FTP

connection

( 88)

How to set up an external visualisation on a Lenze IPC:

1. Go the the \Storage\OCT directory
2. Rename the oct.xml file to oct_save.xml
3. Rename the octvisu.xml file to oct.xml
4. Open the oct.xml file using an editor. This is a text file. For file editing you can for

instance use the Microsoft Editor software.

5. Go to the following section:

6. Enter the IP address of the Lenze control IPC.
7. Line contents (example):

8. Save the changed file on the CF card.
9. Restart visualisation IPC.

• The OPC servers of the control IPC can now be accessed.

Tip!
To undo faulty changes in the configuration files, the original state of the

configuration files can be restored. For this, delete all configuration files from the
\Storage\OCT

directory and restart the Industrial PC.

<Server ID="RemoteIPC" URL="tpda://172.31.207.56:56765" ProvideItems="dynamic"
ItemPre-fix="RemoteIPC" EstablishConnection="on demand"/>

<Server ID="RemoteIPC" URL="tpda://192.168.5.99:56765" ProvideItems="dynamic"
ItemPre-fix="RemoteIPC" EstablishConnection="on demand"/>