Industrial PC | Parameter setting & configuration

Visualisation with »VisiWinNET®«

Configuration of the OPC tunnel

Preparation

Install the OPC tunnel on the Windows XP IPC.

1. The required installation files are provided on the Lenze installation CD in the

following directory:

2. Execute the Setup_OPC_Tunnel_Vxxx.exe installation file.

How to set up the external visualisation:

1. Open the Windows Explorer on the visualisation IPC
2. Go to the following directory: ... \Programs\Lenze\Lenze Digitec OPC

Tunnel

3. Open the oct.xml file using an editor.

• The file can for instance be edited using the Microsoft Editor

4. Go to the following file section:

• Remove the "<!-" and "-->" comment characters at the beginning and at the

end of the section.

5. Enter the IP address of the Lenze control IPC.

• In the example, the line contents is now as follows:

6. Save the changed file.
7. Restart visualisation IPC.

• The OPC servers of the control IPC can now be accessed.

<!--

<Server ID="RemoteIPC" URL="tpda://172.31.207.16:56765"

ProvideItems="dynamic" ItemPre-fix="RemoteIPC" EstablishConnection="on demand">
<FilterFile Path=""/>

</Server>-->

<Server ID="RemoteIPC" URL="tpda://192.168.5.99:56765" ProvideItems="dynamic"
ItemPre-fix="RemoteIPC" EstablishConnection="on demand"> <FilterFile Path=""/>

</Server>