Industrial PC | Parameter setting & configuration

Parameter reference

Industrial PC extension modules

188

L

2.5 EN - 01/2012

C1096/29

C1096/30

C1096/31

C1096/32

C1096/33

Parameter | Name:

C1096/29 | ECAT: Forwarded Rx error counter - port 1

Data type: UNSIGNED_8

Index: 23479.29

d

=

0x5BB7.0x1D

h

Number of errors that occurred during data reception at port 1 for those slaves standing in line before the current

slave in bus topology.
Display range

(min. value | unit | max. value)

0

255

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1096/30 | ECAT: Forwarded Rx error counter - port 2

Data type: UNSIGNED_8

Index: 23479.30

d

=

0x5BB7.0x1E

h

Number of errors that occurred during data reception at port 2 for those slaves standing in line before the current

slave in bus topology.
Display range

(min. value | unit | max. value)

0

255

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1096/31 | ECAT: Forwarded Rx error counter - port 3

Data type: UNSIGNED_8

Index: 23479.31

d

=

0x5BB7.0x1F

h

Number of errors that occurred during data reception at port 3 for those slaves standing in line before the current

slave in bus topology.
Display range

(min. value | unit | max. value)

0

255

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1096/32 | ECAT: Error counter processing unit

Data type: UNSIGNED_8

Index: 23479.32

d

=

0x5BB7.0x20

h

Number of errors that occurred in the processing unit.

EtherCAT slave controller error counter register "0x030C": Internal error of the slave
Display range

(min. value | unit | max. value)

0

255

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1096/33 | ECAT: PDI error counter

Data type: UNSIGNED_8

Index: 23479.33

d

=

0x5BB7.0x21

h

Number of internal errors of the slave, reported by the process data interface.
Display range

(min. value | unit | max. value)

0

255

;

Read access … Write access … CINH … PLC STOP … No transfer