Industrial pc | parameter setting & configuration – Lenze PC-based Automation Industrial PC User Manual

Page 182

Advertising
background image

Industrial PC | Parameter setting & configuration

Parameter reference

Industrial PC extension modules

182

L

2.5 EN - 01/2012

C1096/9

C1096/10

C1096/11

Parameter | Name:

C1096/9 | ECAT config.: Physical address

Data type: UNSIGNED_16

Index: 23479.9

d

=

0x5BB7.0x09

h

The physical address of the slave set in the master configuration file

This address is specified by the »PLC Designer« and assigned consistently in ascending order, starting with 1001.
Display range

(min. value | unit | max. value)

0

65536

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1096/10 | ECAT: Alias address

Data type: UNSIGNED_16

Index: 23479.10

d

=

0x5BB7.0x0A

h

Alias addresses are addresses directly saved on the device (e.g. via DIP switches)

At present our system does not support alias addresses.
Display range

(min. value | unit | max. value)

0

65536

;

Read access … Write access … CINH … PLC STOP … No transfer

Parameter | Name:

C1096/11 | ECAT: Port state

Data type: BITFIELD_16

Index: 23479.11

d

=

0x5BB7.0x0B

h

Display of the port states/connections (ports 0 ... 3) of a slave

The structure is bit-coded (WORD).
Value is bit-coded:

Bit 0 Port 0

1 (TRUE) = Slave is

connected (logic result of

bits 0 ... 11)

Bit 1 Port 1
Bit 2 Port 2
Bit 3 Port 3
Bit 4 Port 0

1 (TRUE) = Link is known

Bit 5 Port 1
Bit 6 Port 2
Bit 7 Port 3
Bit 8 Port 0

1 (TRUE) = Loop is closed

Bit 9 Port 1

Bit 10 Port 2
Bit 11 Port 3
Bit 12 Port 0

1 (TRUE) = Signal received

Bit 13 Port 1
Bit 14 Port 2
Bit 15 Port 3

;

Read access … Write access … CINH … PLC STOP … No transfer