Industrial PC | Parameter setting & configuration

IPC backup & restore

Software update procedure

9.7

Software update procedure

Steps to be carried out in the case of R1.5:

How to identify the currently installed version:

In the web-based parameterisation the software version can be found under:

• Parameter list 1 -> Device: Software version
• The first two version numbers are important.

Carrying out a SW update of R1.5
When you install an update of R1.5, e. g. to R2.0, you have to carry out the following steps:

How to carry out an R1.5 software update:

1. Prepare USB stick for an update with »IPC Backup & Restore« under Windows® XP.
2. Connect USB stick to the running Industrial PC
3. Copy the BackupRestoreX86Rel.Cab from directory

\USBStorage\<UpdatePaket>\CAB\ BackupRestoreX86Rel.Cab

to

\Storage\BackupRestoreX86Rel.Cab under Windows® CE.

4. Remove USB stick.
5. Restart Industrial PC.

• By this the new runtime environment is extracted.

6. Restart Industrial PC with the USB stick prepared.

Note!

Lenze recommend archiving the Compact Flash card using »IPC Backup &

Restore« under Windows® XP before carrying out a software update.